• TECHNICAL CHARACTERISTICS:

    • „C” or „L” profile frame made of zinc plated steel sheet 3 mm thick with EPDM gasket on three edges
    • door leaves made of zinc plated steel sheet 1,5 mm thick
    • door leaves 90 mm thick without additional finishes with EPDM gasket and intumescent fire gaskets on four edges
    • filled with mineral wool of a density 100kg/m3 and gypsum boards
    • eight hinges with ball bearings
    • six anti-burglary bolts
    • main lock: multipoint class 7 according to EN 12209
    • ·door closer
    • two manual, semiautomatic or automatic flush bolts
    • additional lock (optional)
    • electric strike or solenoid or electric deadbolt (optional)

     

    PARAMETERS:

    • burglary resistance – class RC4 according to EN 1627: 2012 
    • fire resistance – EI30, EI60 according to EN 16034: 2014
    • acoustic insulation – Rw= 47 dB according to EN ISO 717-1: 1999
    • thermal transmittance – 1,3 Uw(W/m2K) according to EN ISO10077-1: 2007
    • wind load resistance – class 5C according to EN 12210: 2001
    • smoke tightness – Sa, S200 according to EN 16034: 2014
    • self-closing – class C according to EN 16034: 2014
    • dangerous substances – PZH approval according to EN 14351-1+A1: 2010
    • water resistance – class 3B according to EN 12208: 2001
    • air permeability – class 3 according to EN 12207: 2001
    • operating forces – class 2 according to EN 12217: 2005
    • mechanical strength – class 4 according to EN 1192: 2001

     

    APPLICATION:

    • residential, storage, commercial, garage facilities and technical rooms exposed to burglary with the fire resistance requirement EI30 or EI60
    • military, police, prison facilities where RC4 class security and fire resistance EI30 or EI60 are required
    • lower security bank facilities and facilities related to cash handling where fire resistance EI30 or EI60 is required
    • power and telecommunication facilities with a high degree of protection against burglary, which require fire resistance EI30 or EI60
    • all other facilities where doors are used in hard conditions where fire resistance EI30 or EI60 is required